450/750VPVC insulated electric wire

450/750VPVC insulated electric wire
Product Detailed
Related Categories:Electrical Wires
We produce pvc electric wire CE certification Fast delivery &best price More than 20 years' experience

Wire / PVC Insulated Electrical Wire/ 450/750V Wire

PVC Wire is used for lighting, electronic equipment, instument and communication equipment with rated voltage 450/750V or less

Specification:

1. The rated voltage of the wires should equal to or higher then the rated voltage of the system when wires are used at AC system. If the wires are used at DC system, the rated voltage of system should lower then 1.5 times as high as rated voltage of cable and wires. The working voltage of the system could be 1.1 times as high as the rated voltage of the cable.

2. The long term working temperature should lower then 70oC. The working temperature of BV-90 should lower then 90oC. And the laying temperature should higher then 0oC.3. The curve diameter of the wire should longer than 8 times of the diameter of the outer diameter of cable and wires if their outer diameter is 25 mm or above. If the diameter of cable and wires is above 25 mm, the curve diameter should be at least 12 times of the outer diameter of the cable and wires.

Type

Model

Name

BV

Copper core PVC insulation power line

BLV

Aluminium core PVC insulation power line

BVR

Copper core PVC insulation flexible power line

BVV

Copper core PVC insulation PVC sheath round power line

BVVB

Copper core PVC insulation PVC sheath parellel power line

BLVVB

Aluminium core PVC insulation PVC sheath parellel power line

BV-105

Copper core heat-resistance 105oC PVC insulation

Specifications

BVVB/BLVVB 450/750V

Nominal Section sqmm

Number /Diameter of core

mm

Maximum Outer Diamater mm

Reference Weight

Kg/km

Conductor resistance at 20°C (Ω/km)

Al

Cu

Cu

Al

Cu

Al

2*0.75

2*1/0.97

4.6*7.0

43.7

24.5

2*1.0

2*1/1.13

4.8*7.4

51.0

18.1

2*1.5

2*1/1.38

5.4*8.4

65.9

12.1

2*2.5

2*1/1.78

6.2*9.8

6.2*9.8

95.7

64.9

7.41

11.8

2*4

2*7/0.85

6.8*11.0

7.2*11.5

146.0

80.7

4.61

7.39

2*6

2*7/1.04

7.4*12.0

8.0*13.0

200.0

104

3.08

4.91

2*10

2*7/1.35

9.6*16.0

9.6*16.0

323.0

177

1.83

3.08

3*0.75

3*1/0.97

4.6*9.4

62.6

24.50

3*1.0

3*1/1.13

4.8*9.8

74.3

18.10

3*1.5

3*1/1.38

5.4*11.5

95.6

12.10

3*2.5

3*1/1.78

6.2*13.5

6.2*13.5

140

93.9

7.41

11.8

3*4

3*7/0.85

7.0*15.0

7.4*16.5

220

123

7.41

7.39

3*6

3*7/1.04

7.4*17.0

8.0*18.0

295

153

4.61

4.91

3*10

3*7/1.35

9.6*22.5

9.6*22.5

485

261

1.83

3.08